i.LON® 600 LonWorks®/IP Server
The i.LON® 600 LonWorks®/IP Server is an ISO/IEC 14908 router that uses IP as a standard LonWorks channel to allow LonWorks devices such as pumps, motors, valves, sensors, and lights to be securely configured, monitored, and controlled over IP or Ethernet.
- Allows the resident IP network to be used as a standard LonWorks media type alongside twisted pair, power line, coax, IR and others
- Creates a local or remote control network connection for a LonWorks Network Services (LNS®) or OpenLDV application, which could then manage, monitor, and control many LonWorks control networks when an i.LON 600 server is installed in each of them
- Offers unparalleled packet throughput, rugged construction, and simple commissioning; Provides for flexible network designs with both TP/FT-10 (78kbps) and TP/XF-1250 (1.25Mbps) channel options
- Supports internetworking of up to 256 i.LON 600 servers and operation of multiple i.LON servers behind a Network Address Translation (NAT) firewall
- Installs using standard tools such as the LonMaker® Integration Tool or can be setup to self-install using parameters on a Web page
See the i.LON 600 LonWorks/IP Server datasheet (PDF) for complete specifications.
Minimum PC requirements for configuration server software: Pentium II @ 600 MHz, 128kb RAM, 10MB free disk space
Processor: AMD au1000 32-bit RISC
Channel Type: TP/FT-10 (78kbps), Models 72601 and 72603; TP/XF-1250 (1.2Mbps), Models 72602 and 72604
LonWorks Twisted Pair Connector: Screw terminals
Ethernet Port: 10/100 BaseT, auto-selecting, auto polarity
Ethernet Connector: RJ-45
Console Interface: EIA-232, 9600 baud (8 data bits, no parity, 1 stop bit)
Console Connector : DB-9
Operating Input Voltage: +24Vac or Vdc, +33%, <15W (Models 72603 and 72604); 90V–240Vac or Vdc, 50–60Hz (Models 72601 and 72602)
i.LON 600 LonWorks/IP Server datasheet (PDF)
i.LON 600 LonWorks/IP Server Quick Start (PDF)
i.LON 600 LonWorks/IP ServerUser's Guide (PDF)
Considerations for Securing Building Automation System (BAS) Networks (PDF)
i.LON® 600 Router How-tos
How-to instructions for some common routing applications
Register for free online eTraining, including this course and others:
Using the i.LON to Interface LonWorks Devices to TCP/IP Networks
Learn how to design, integrate, and troubleshoot IP-852- and RNI TCP/IP-based LonWorks networks (Free, eTraining course, 2:06 hr).
i.LON 600 / 1000
i.LON 600 & 1000 repeater configuration files